Home & workshop Heating & cooling

Radiator size calculator

Measure in
Room length
Room width
Ceiling height
Construction
Room type
Output per radiator
W
Heat output needed 1,344 W
33.6 m³ × 40 W/m³ for a living
In BTU per hour 4,586
In kilowatts 1.34 kW
Radiators at that output 2
Room volume 33.6 m³
Watts per m³ used 40
Watts per m³ by construction · quoted at ΔT 50

A sizing estimate. Radiator outputs are quoted at a specific flow temperature — a heat pump running at 45 °C gets far less from the same radiator than a boiler at 75 °C.

Radiator sizing starts from room volume rather than floor area. A standard-construction living room wants about 40 watts per cubic metre, so a 4 × 3.5 m room with 2.4 m ceilings is 33.6 m³ and needs 1,344 W, or 4,586 BTU per hour. Every one of those figures assumes the radiator is quoted at Delta T 50.

How to size a radiator

1 Enter the room size including the ceiling height, since heat loss follows volume.
2 Pick the construction type. Modern to poorly insulated is a range of 30 to 70 W per cubic metre, so it more than doubles the answer.
3 Choose the room type. A bathroom adds twenty per cent, a bedroom or kitchen takes ten off, a conservatory adds half again.
4 Check what Delta T the radiator you are looking at was rated at, because a figure without one is not a figure.
5 If the system is a heat pump, take roughly a third of the catalogue output and size from that.

The trap in radiator sizing is not the room, it is the temperature the output was measured at. European radiators are tested to EN 442, whose reference condition is 75 °C flow, 65 °C return and a 20 °C room. Average the flow and return and the water is at 70, which is fifty degrees above the room, and that is the Delta T 50 every catalogue figure is quoted at. Change the water temperature and the output changes with it, along a curve rather than in proportion: output scales as the temperature difference divided by fifty, raised to the radiator’s own exponent. EN 442-2 measures that exponent for each model alongside its output, and it is on the datasheet; 1.3 is the value conventionally used for a panel radiator when the real one is not to hand, and it is what every figure below comes from.

Work that curve through and the numbers are stark. A boiler at 75/65 gives you the rated output, by definition. A system run at Delta T 30 gives about 52 per cent of it. A heat pump flowing at 45 °C with a five degree drop across the radiator averages 42.5, so Delta T 22.5, and the same radiator delivers around 35 per cent of its catalogue figure. That single fact is why converting a house to a heat pump means upsizing radiators, and it also explains why an old catalogue can look so generous: British manufacturers once quoted at Delta T 60, which flatters the same radiator by 27 per cent against a modern Delta T 50 figure.

The volume rule underneath all this is deliberately coarse, and its coarseness sits mostly in the construction setting. Modern and well insulated is 30 W per cubic metre; poorly insulated is 70. Those two multiply the same room by more than two, and no other input here comes close to that leverage, so it is the one to get right rather than guess. The room-type factor is smaller and mostly about how the room is used: a bathroom adds twenty per cent because people stand still in it while wet, a bedroom drops ten because it is heated to a lower target, and a kitchen drops ten because ovens, hobs and a fridge are all quietly contributing.

The radiator count is a division and should be read as one. A 1,344 W room served by 1,000 W radiators comes out as two, which is 2,000 W of radiator for a 1,344 W load. Radiators are not sold in that few sizes, so the useful reading is the watts, not the count: one radiator of roughly 1,400 W, or two of 700, either of which fits the room better than the rounding does. Deliberate oversizing is fine here in a way it never is with cooling, because a larger radiator simply reaches the room temperature at a lower flow temperature, and a lower flow temperature is where both a condensing boiler and a heat pump do their best work.

What people use it for

  • Replacing a single radiator in an existing room
  • Sizing radiators for an extension or a loft conversion
  • Checking whether existing radiators will cope with a heat pump
  • Converting a catalogue output between Delta T ratings
  • Comparing towel rail outputs for a bathroom
  • Translating a watts figure into the BTU a UK merchant quotes
  • Working out whether one large radiator or two small ones suits a room

Questions

Sizing works better on volume. About 40 W per cubic metre for standard construction, 30 for a modern insulated build, 55 for an older solid-wall house and up to 70 for a poorly insulated one.

BS EN 442-2:2014, radiators and convectors — test methods and rating (BSI catalogue entry; the standard is paywalled)
Was this tool any good?
Internal signal only · I use it to find the tools worth rebuilding